1471
UnclassifiedSpeed
What This Code Means
Engine failed to crank after the generator control received a start signal; Generator set output current has exceeded the warning limit threshold for greater than the fixed time delay; Generator set output current has exceeded the shutdown limit threshold for greater than the fixed time delay; Engine RPM has decreased to zero while not in run at rated mode; Engine RPM has decreased to zero, while not in run at rated mode
Possible Causes
- •Alternator output current (one or more phases) has exceeded safe operating limits
- •Base board or harness connection fault
- •Dead or weak battery
- •Failed starter
- •Generator set overload
- •Incorrect calibration in the PowerCommand control
- •Incorrect rating setup in control
- •Individual phase of alternator output current exceeded high current threshold of rated output current continuously for more than set time delay
- •Short or overload
Suggested Actions
- 1Attempt to start the generator and test for B+ at the starter supply lug
- 2Charge or replace the battery as necessary
- 3Check continuity from P12 to the CTs (P12-1 to P12-4, P12-2 to P12-5, P12-3 to P12-6)
- 4Check if starter is defective if B+ is present at the starter supply lug
- 5Check load lead connections
- 6Check the load
- 7Check the rating setup in the control and correct if necessary
- 8Disconnect the AC harness from the load cables
- 9If B+ is present at the starter supply lug, the starter could be defective
- 10Inspect the AC harness and board connector pins
- 11Inspect the load cables and the AC harness connections
- 12Press the Reset/Fault acknowledge button on the display
- 13Reduce the generator set load by powering off unnecessary electrical loads
- 14Remove connector P12 from the Base board
- 15Repair harness/connector connections
- 16Verify battery voltage is at least 12 VDC (or 24 VDC if applicable)