121

UnclassifiedSpeed

What This Code Means

No B+ present at starter during start attempt; No B+ present at starter relay - COM lead; No B+ present at starter relay - N/O terminal during start attempt; Open circuit between TB1-15 and TB1-16

Possible Causes

  • •Cold engine
  • •Corroded, bent, broken, pushed back, expanded, or loose pins
  • •Defective Base board
  • •Defective Emergency Stop switch
  • •Defective Emergency Stop wiring
  • •Defective MPU or circuit
  • •Defective starter
  • •Defective starter relay
  • •Dirt or debris in or on the connector pins
  • •Electronic governor actuator could be bad
  • •Evidence of moisture in or on the connector
  • •Fault simulation was enabled with InPower
  • •Fault threshold is not set correctly with InPower
  • •Faulty Crankshaft Speed Sensor
  • •Faulty Crankshaft Speed Sensor Connections
  • •Faulty crankshaft speed sensor
  • •Faulty crankshaft speed sensor connections
  • •MPU/circuit or Base board is defective
  • •Missing or damaged connector seals
  • •Moisture in or on the connector
  • •No magnetic pickup pulses are sensed for a Loss of Speed delay
  • •No magnetic pickup pulses sensed for a Loss of Speed delay
  • •Open circuit between starter relay − COM and battery B+
  • •Open circuit between starter relay − N/O and SW terminal of starter
  • •Restricted fuel supply (clogs or leaks in fuel supply)
  • •Single step large block load removal
  • •Speed Signal Lost (Loss of Speed Sense)
  • •Speed signal lost
  • •The electronic governor actuator could be bad

Suggested Actions

  1. 1Attempt to start and test for B+ at the starter
  2. 2Check continuity between J25-2 and J25-6
  3. 3Check for an open circuit between starter relay − COM and battery B+
  4. 4Check for an open circuit between starter relay − N/O and SW terminal of starter
  5. 5Check the crankshaft speed sensor supply voltage
  6. 6Check the crankshaft speed sensor supply voltage.
  7. 7Check wiring continuity and test starter relay
  8. 8Clear fault and restart genset
  9. 9Contact an authorized service center for assistance
  10. 10Determine highest allowable setting and set threshold as required
  11. 11Determine highest allowable setting and set threshold as required using InPower
  12. 12Disconnect the engine harness connector from the crankshaft speed sensor
  13. 13Disconnect the engine harness connector from the crankshaft speed sensor.
  14. 14Ensure adequate fuel supply that is free of clogs or leaks
  15. 15Immediate repair by trained and experienced service personnel
  16. 16Inspect for corroded, bent, broken, pushed back, expanded, or loose pins
  17. 17Inspect for corroded, bent, broken, pushed back, expanded, or loose pins.
  18. 18Inspect for dirt or debris in or on the connector pins
  19. 19Inspect for dirt or debris in or on the connector pins.
  20. 20Inspect for evidence of moisture in or on the connector
  21. 21Inspect for evidence of moisture in or on the connector.
  22. 22Inspect for missing or damaged connector seals
  23. 23Inspect for missing or damaged connector seals.
  24. 24Inspect or repair O-rings and pump
  25. 25Inspect or repair O-rings, pump
  26. 26Inspect the crankshaft speed sensor and the engine harness connector pins
  27. 27Inspect the crankshaft speed sensor and the engine harness connector pins.
  28. 28Install the speed sensor breakout cable between the sensor and the sensor harness connector
  29. 29Install the speed sensor breakout cable between the sensor and the sensor harness connector.
  30. 30Isolate to Emergency Stop switch and wiring if circuit is open
  31. 31Monitor engine RPM using InPower (refer to fault code 121)
  32. 32Monitor the engine RPM using a PC-based service tool
  33. 33Reconnect lead COM to starter relay
  34. 34Refer to Fault Code 121 for corrective action
  35. 35Refer to Fault Code 121 instructions
  36. 36Refer to fault code 121
  37. 37Refer to the Fault Code 121 instructions
  38. 38Refer to the engine service manual
  39. 39Remove battery power from control (if InPower is not available)
  40. 40Remove lead from starter relay − N/O, attempt to start, and check for B+ at terminal starter relay − N/O
  41. 41Remove the lead from starter relay − COM and check for B+ at lead COM
  42. 42Reset the control
  43. 43Test the starter per engine service manual and replace if necessary
  44. 44Verify that fault is not enabled
  45. 45Verify that fault is not enabled (if no InPower, remove battery power from control)
  46. 46With Emergency Stop push button not activated, remove configurable leads from TB1-15 and TB1-16 and check for continuity
  47. 47With Local Emergency Stop push button not activated, remove P25 from Base board and check for continuity between J25-2 and J25-6