121
UnclassifiedSpeed
What This Code Means
No B+ present at starter during start attempt; No B+ present at starter relay - COM lead; No B+ present at starter relay - N/O terminal during start attempt; Open circuit between TB1-15 and TB1-16
Possible Causes
- •Cold engine
- •Corroded, bent, broken, pushed back, expanded, or loose pins
- •Defective Base board
- •Defective Emergency Stop switch
- •Defective Emergency Stop wiring
- •Defective MPU or circuit
- •Defective starter
- •Defective starter relay
- •Dirt or debris in or on the connector pins
- •Electronic governor actuator could be bad
- •Evidence of moisture in or on the connector
- •Fault simulation was enabled with InPower
- •Fault threshold is not set correctly with InPower
- •Faulty Crankshaft Speed Sensor
- •Faulty Crankshaft Speed Sensor Connections
- •Faulty crankshaft speed sensor
- •Faulty crankshaft speed sensor connections
- •MPU/circuit or Base board is defective
- •Missing or damaged connector seals
- •Moisture in or on the connector
- •No magnetic pickup pulses are sensed for a Loss of Speed delay
- •No magnetic pickup pulses sensed for a Loss of Speed delay
- •Open circuit between starter relay − COM and battery B+
- •Open circuit between starter relay − N/O and SW terminal of starter
- •Restricted fuel supply (clogs or leaks in fuel supply)
- •Single step large block load removal
- •Speed Signal Lost (Loss of Speed Sense)
- •Speed signal lost
- •The electronic governor actuator could be bad
Suggested Actions
- 1Attempt to start and test for B+ at the starter
- 2Check continuity between J25-2 and J25-6
- 3Check for an open circuit between starter relay − COM and battery B+
- 4Check for an open circuit between starter relay − N/O and SW terminal of starter
- 5Check the crankshaft speed sensor supply voltage
- 6Check the crankshaft speed sensor supply voltage.
- 7Check wiring continuity and test starter relay
- 8Clear fault and restart genset
- 9Contact an authorized service center for assistance
- 10Determine highest allowable setting and set threshold as required
- 11Determine highest allowable setting and set threshold as required using InPower
- 12Disconnect the engine harness connector from the crankshaft speed sensor
- 13Disconnect the engine harness connector from the crankshaft speed sensor.
- 14Ensure adequate fuel supply that is free of clogs or leaks
- 15Immediate repair by trained and experienced service personnel
- 16Inspect for corroded, bent, broken, pushed back, expanded, or loose pins
- 17Inspect for corroded, bent, broken, pushed back, expanded, or loose pins.
- 18Inspect for dirt or debris in or on the connector pins
- 19Inspect for dirt or debris in or on the connector pins.
- 20Inspect for evidence of moisture in or on the connector
- 21Inspect for evidence of moisture in or on the connector.
- 22Inspect for missing or damaged connector seals
- 23Inspect for missing or damaged connector seals.
- 24Inspect or repair O-rings and pump
- 25Inspect or repair O-rings, pump
- 26Inspect the crankshaft speed sensor and the engine harness connector pins
- 27Inspect the crankshaft speed sensor and the engine harness connector pins.
- 28Install the speed sensor breakout cable between the sensor and the sensor harness connector
- 29Install the speed sensor breakout cable between the sensor and the sensor harness connector.
- 30Isolate to Emergency Stop switch and wiring if circuit is open
- 31Monitor engine RPM using InPower (refer to fault code 121)
- 32Monitor the engine RPM using a PC-based service tool
- 33Reconnect lead COM to starter relay
- 34Refer to Fault Code 121 for corrective action
- 35Refer to Fault Code 121 instructions
- 36Refer to fault code 121
- 37Refer to the Fault Code 121 instructions
- 38Refer to the engine service manual
- 39Remove battery power from control (if InPower is not available)
- 40Remove lead from starter relay − N/O, attempt to start, and check for B+ at terminal starter relay − N/O
- 41Remove the lead from starter relay − COM and check for B+ at lead COM
- 42Reset the control
- 43Test the starter per engine service manual and replace if necessary
- 44Verify that fault is not enabled
- 45Verify that fault is not enabled (if no InPower, remove battery power from control)
- 46With Emergency Stop push button not activated, remove configurable leads from TB1-15 and TB1-16 and check for continuity
- 47With Local Emergency Stop push button not activated, remove P25 from Base board and check for continuity between J25-2 and J25-6