UF

UnclassifiedElectrical

What This Code Means

Engine starting battery voltage rises above 16 VDC for more than 30 seconds when the engine is running; Engine starting battery voltage falls below 11 VDC for more than 30 seconds when the engine is not running

Possible Causes

  • •Battery charger operation
  • •Battery rating and condition
  • •Governed frequency falls 1Hz below the system frequency setting for more than 60 seconds
  • •Governed frequency falls below 90% of nominal system frequency for more than 5 seconds
  • •Governed frequency falls below 90% of the nominal system frequency for more than 5 seconds
  • •Governed frequency falls below 90% of the nominal system frequency for more than 5 seconds or below 59 Hz for more than 60 seconds
  • •Governed frequency falls below 90% of the nominal system frequency for more than 5 seconds or below 59Hz for more than 60 seconds
  • •Governed frequency falls below 90% of the system frequency setting for more than 5 seconds
  • •Voltage or frequency out of range

Suggested Actions

  1. 1Charge or replace the battery
  2. 2Check the battery charger operation
  3. 3Check the battery rating and condition
  4. 4Contact an authorized Kohler distributor/dealer for service if problem continues
  5. 5Contact an authorized distributor/dealer for service if problem continues
  6. 6Reduce the load and restart the generator set
  7. 7Reset fault shutdown condition using the generator set master switch (OFF/RESET)