NO CURRENT SHUTDOWN

UnclassifiedGeneral

What This Code Means

Generator shuts down; RDC2 controller displays "No Current Shutdown"

Possible Causes

  • •AC output wires are not crossing through the CT in opposite directions
  • •CT is not connected to the generator controller at P3

Suggested Actions

  1. 1Verify that the AC output wires cross through the CT in opposite directions
  2. 2Verify that the CT is connected to the generator controller at P3
  3. 3Correct wiring and retry the current metering test from step 1 in Section 4.6