NO CURRENT SHUTDOWN
UnclassifiedGeneral
What This Code Means
Generator shuts down; RDC2 controller displays "No Current Shutdown"
Possible Causes
- •AC output wires are not crossing through the CT in opposite directions
- •CT is not connected to the generator controller at P3
Suggested Actions
- 1Verify that the AC output wires cross through the CT in opposite directions
- 2Verify that the CT is connected to the generator controller at P3
- 3Correct wiring and retry the current metering test from step 1 in Section 4.6