MAX. CLOSE ATTEMPTS HIGH WARNING

UnclassifiedTransfer Switch

What This Code Means

Controller tries multiple times to close the contactor in the paralleling box without success

Possible Causes

  • •Control cable connected incorrectly
  • •Blown or damaged fuses in the contactor close circuit
  • •Control harness connector pins bent, damaged, or corroded
  • •Programmable digital output 1:2 or 116 in SiteTech not enabled or event not set to Contactor
  • •Damaged or incorrectly connected wiring in the generator set or paralleling box
  • •Sync Mode set to Off disabling synchronization and closure to a live bus

Suggested Actions

  1. 1Make sure that the control cable is connected correctly
  2. 2Ensure fuses in the contactor close circuit are intact
  3. 3Inspect control harness connectors to ensure pins are not bent, damaged, or corroded
  4. 4Check programmable digital output 1:2 or 116 in SiteTech to ensure it is enabled and the event is set to Contactor
  5. 5Verify that wiring in the generator set and paralleling box is undamaged and connected correctly
  6. 6Verify the Sync Mode (ensure it is set to Active or Passive rather than Off)