MAX. CLOSE ATTEMPTS HIGH WARNING
UnclassifiedTransfer Switch
What This Code Means
Controller tries multiple times to close the contactor in the paralleling box without success
Possible Causes
- •Control cable connected incorrectly
- •Blown or damaged fuses in the contactor close circuit
- •Control harness connector pins bent, damaged, or corroded
- •Programmable digital output 1:2 or 116 in SiteTech not enabled or event not set to Contactor
- •Damaged or incorrectly connected wiring in the generator set or paralleling box
- •Sync Mode set to Off disabling synchronization and closure to a live bus
Suggested Actions
- 1Make sure that the control cable is connected correctly
- 2Ensure fuses in the contactor close circuit are intact
- 3Inspect control harness connectors to ensure pins are not bent, damaged, or corroded
- 4Check programmable digital output 1:2 or 116 in SiteTech to ensure it is enabled and the event is set to Contactor
- 5Verify that wiring in the generator set and paralleling box is undamaged and connected correctly
- 6Verify the Sync Mode (ensure it is set to Active or Passive rather than Off)