MAX CLOSE ATTEMPTS HIGH
UnclassifiedTransfer Switch
What This Code Means
Controller tried multiple times to close the contactor in the paralleling box without success
Possible Causes
- •Control cable connected incorrectly
- •Blown or damaged fuses in contactor close circuit
- •Bent, damaged, or corroded pins in control harness connectors
- •Programmable digital output 1:2 or 116 in SiteTech not enabled or event not set to Contactor
- •Damaged or incorrectly connected wiring in generator set or paralleling box
Suggested Actions
- 1Make sure that the control cable is connected correctly
- 2Verify fuses in the contactor close circuit are intact
- 3Inspect pins in control harness connectors to ensure they are not bent, damaged, or corroded
- 4Check programmable digital output 1:2 or 116 in SiteTech to ensure it is enabled and the event set to Contactor
- 5Verify that wiring in the generator set and wiring in the paralleling box is undamaged and connected correctly