MAX CLOSE ATTEMPTS HIGH

UnclassifiedTransfer Switch

What This Code Means

Controller tried multiple times to close the contactor in the paralleling box without success

Possible Causes

  • •Control cable connected incorrectly
  • •Blown or damaged fuses in contactor close circuit
  • •Bent, damaged, or corroded pins in control harness connectors
  • •Programmable digital output 1:2 or 116 in SiteTech not enabled or event not set to Contactor
  • •Damaged or incorrectly connected wiring in generator set or paralleling box

Suggested Actions

  1. 1Make sure that the control cable is connected correctly
  2. 2Verify fuses in the contactor close circuit are intact
  3. 3Inspect pins in control harness connectors to ensure they are not bent, damaged, or corroded
  4. 4Check programmable digital output 1:2 or 116 in SiteTech to ensure it is enabled and the event set to Contactor
  5. 5Verify that wiring in the generator set and wiring in the paralleling box is undamaged and connected correctly