HB
UnclassifiedElectrical
What This Code Means
Engine starting battery voltage rises above 16 VDC for more than 30 seconds when the engine is running; Engine starting battery voltage falls below 11 VDC for more than 30 seconds when the engine is not running
Possible Causes
- •Battery charger operation
- •Battery rating and condition
- •Engine starting battery voltage rises above 125% of the battery voltage setting for more than 10 seconds when the engine is running
- •Engine starting battery voltage rises above 16 VDC for a 12 VDC system for more than 10 seconds when the engine is not running
- •Engine starting battery voltage rises above 16 VDC for a 12 VDC system or above 30 VDC for a 24 VDC system for more than 10 seconds when the engine is not running
- •Engine starting battery voltage rises above 16VDC for a 12VDC system or above 30VDC for a 24VDC system for more than 10 seconds when the engine is not running
- •Engine starting battery voltage rises above 30 VDC for a 24 VDC system for more than 10 seconds when the engine is not running
- •High battery voltage
- •Low battery voltage
Suggested Actions
- 1Charge or replace the battery
- 2Check the battery charger operation
- 3Check the battery rating and condition
- 4Correct the battery voltage fault condition