FREQUENCY LOW
What This Code Means
Over Current warning displayed on the controller and/or in OnCue Plus; Over Frequency warning displayed on the controller and/or in OnCue Plus; Under Frequency warning displayed on the controller and/or in OnCue Plus; Loss of Field warning displayed on the controller and/or in OnCue Plus; Over Power warning displayed on the controller and/or in OnCue Plus; Reverse Power warning displayed on the controller and/or in OnCue Plus; Over Voltage warning displayed on the controller and/or in OnCue Plus; Under Voltage warning displayed on the controller and/or in OnCue Plus
Possible Causes
- •Excessive load on generator set
- •Excessive load on the generator set
- •Frequency is <1Hz below the setpoint for more than 60 seconds
- •Frequency is <90% of the setpoint for more than 10 seconds
- •Governed frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below setting for more than 60 seconds
- •La frecuencia regulada cae bajo el 90 % de la configuración de frecuencia del sistema durante más de 10 segundos o 1 Hz bajo la configuración de la frecuencia del sistema durante más de 60 segundos
- •La fréquence régulée est inférieure de 1 Hz à la fréquence de consigne pendant plus de 60 s
- •La fréquence régulée est inférieure à 90 % de la fréquence de consigne du système pendant plus de 10 s
- •La fréquence régulée est inférieure à 90 % de la fréquence de consigne du système pendant plus de 10 s ou inférieure de 1 Hz à la fréquence de consigne pendant plus de 60 s
- •Tripped enclosure thermostat (Model 20RESC/20RESCL only)
Suggested Actions
- 1Contact an authorized dealer for paralleling system installation, startup, troubleshooting, or service
- 2Contact an authorized distributor or dealer for paralleling system troubleshooting or service
- 3Contact an authorized distributor/dealer for service
- 4Contact authorized dealer/distributor for service
- 5Contacte con un distribuidor o proveedor autorizado para solicitar mantenimiento
- 6Model 20RESC/20RESCL only: Check enclosure thermostat and reset if tripped (See Section 5.6)
- 7Press AUTO or OFF to clear the warning (Pressing OFF will stop the generator set)
- 8Press AUTO or OFF to clear the warning display
- 9Press OFF to stop the generator set
- 10Reduce load and restart generator set
- 11Reduce the load and restart the generator set
- 12Reduzca la carga y reinicie el grupo electrógeno
- 13Réduire la charge et redémarrer le groupe électrogène
- 14S’adresser à un concessionnaire/ réparateur agréé
- 15S’adresser à un concessionnaire/réparateur agréé