LB
UnclassifiedElectrical
What This Code Means
Engine starting battery voltage rises above 16 VDC for more than 30 seconds when the engine is running; Engine starting battery voltage falls below 11 VDC for more than 30 seconds when the engine is not running
Possible Causes
- •Battery charger operation
- •Battery rating and condition
- •Engine starting battery voltage falls below 16 VDC for a 24 VDC system for more than 10 seconds when the engine is not running
- •Engine starting battery voltage falls below 8 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system for more than 10 seconds when the engine is not running
- •Engine starting battery voltage falls below 9.5 VDC for a 12 VDC system for more than 10 seconds when the engine is not running
- •Engine starting battery voltage falls below 9.5VDC for a 12VDC system or below 16VDC for a 24VDC system for more than 10 seconds when the engine is not running
- •Engine starting battery voltage falls below the battery voltage setting (typically 12 volts) for more than 90 seconds when the engine is not running
- •Faulty battery charger operation
- •High battery voltage
- •Improper battery rating or degraded battery condition
- •Low battery voltage
- •Low charging battery
Suggested Actions
- 1Charge or replace the battery
- 2Check the battery charger operation
- 3Check the battery rating and condition
- 4Correct the battery voltage fault condition
- 5Reset fault shutdown condition using the generator set master switch (OFF/RESET)