FAIL TO SYNC
UnclassifiedGeneral
What This Code Means
Sources did not synchronize within the Fail to Sync time delay on closed-transition models
Possible Causes
- •Generator set frequency misadjustment
- •Incorrect inphase monitor angle
- •Incorrect synchronization settings for voltage differential, frequency differential, or phase angle
- •Two sources fail to come into synchronization within specified phase angle
- •Two sources fail to come into synchronization within specified phase angle within allowed time
- •Two sources fail to come into synchronization within specified phase angle within the allowed time (default 30 sec)
Suggested Actions
- 1Adjust inphase monitor angle
- 2Adjust the generator set frequency in order to achieve source synchronization
- 3Check synchronization settings for voltage differential, frequency differential, and phase angle (See TP-6714, MPAC 1500 Controller Operation Manual)
- 4Check the synchronization settings for voltage differential, frequency differential, and phase angle (See Controller Operation Manual)
- 5Connect IPM Synching output to customer-supplied equipment to boost the generator set if the sources do not synchronize
- 6Connect the IPM Synching output to customer-supplied equipment to boost the generator set if sources do not synchronize
- 7Set the programmed-transition override function to allow a programmed-transition transfer if sources do not synchronize (See TP-6714 for instructions)
- 8Set the programmed-transition override function to allow a programmed-transition transfer in the event that the sources do not synchronize