F5

UnclassifiedLubrication

What This Code Means

No voltage measured at pin 3O on the ECM connector; ECM firmware version reads unknown; No voltage measured in Step 11 (of a procedure not fully detailed); Steps 4 and 6 tested good (of a procedure not fully detailed); Step 14 tested bad (of a procedure not fully detailed); Step 14 tested good (of a procedure not fully detailed); CAN bus communication failure between ECM and controller; Wire 608 to ground has low resistance on the coil of the relay.; Wire 14F to ground shows DC battery voltage.; Wire 13 has no or low battery voltage at the relay.

Possible Causes

  • Blown in-line 15-amp fuse in the harness
  • Faulty Wire 601 between the controller and the low fuel pressure switch
  • Faulty printed circuit board
  • Issue with CAN bus communication lines (Wires 743a and 744a)
  • Issue with termination resistors
  • Issue with wiring harness continuity
  • Faulty F5 fuse
  • Break in the wire between the relay and the battery

Suggested Actions

  1. 1Check the in-line 15-amp fuse in the harness (located roughly 6 inches from the starter) and repair as needed.
  2. 2Repair or replace Wire 601 between the controller and the low fuel pressure switch.
  3. 3Replace printed circuit board.
  4. 4Check firmware for updates.
  5. 5Check for battery voltage at pin 3O on the ECM connector.
  6. 6Check the in-line 15-amp fuse in the harness.
  7. 7Check for battery voltage at pin 2O on the ECM connector (Wire 172) while pressing manual start.
  8. 8Replace F5 fuse
  9. 9Test the harness back toward the battery looking for a break in the wire.