BATTERY CHARGER AC FAILURE ALARM
UnclassifiedLubrication
What This Code Means
Battery Charger AC Failure Alarm; No oil pressure after 10 seconds
Possible Causes
- •120 VAC is not present
- •Unknown (requires engine service manual reference)
Suggested Actions
- 1Measure for AC volts at Connector PZ7.
- 2If 120 VAC is present at Connector PZ7 the problem is in the control panel.
- 3If 120 VAC is not present measure for AC volts at the corresponding locations on the TB2 connector.
- 4If TB2 test is good, measure for AC volts at the source of the fused 120 VAC for T1 and neutral wire.
- 5Shut the unit down and reference the engine service manual.