F2

UnclassifiedGeneral

What This Code Means

Generator set will not produce any power; Generator's excitation system does not build up

Possible Causes

  • Loss of residual magnetism in the generator

Suggested Actions

  1. 1Flash the generator set to restore residual magnetism by performing the following steps:
  2. 2Disconnect exciter winding leads F1 and F2 from the voltage regulator
  3. 3Start the generator set
  4. 4With the generator set running, apply 12VDC from a wet cell battery (automotive type) to the F1 and F2 exciter winding leads for 1 second
  5. 5Stop the generator set and reconnect the F1 and F2 leads to the voltage regulator

ASK RUDY ABOUT THIS FAULT

Get a diagnosis walkthrough for F2 on your specific Baldor unit — cited to the OEM manual, not a forum guess.

TRY IT FREE