F1
UnclassifiedGeneral
What This Code Means
Generator set will not produce any power; Generator's excitation system does not build up
Possible Causes
- •Loss of residual magnetism in the generator
Suggested Actions
- 1Flash the generator set to restore residual magnetism by performing the following steps:
- 2Disconnect exciter winding leads F1 and F2 from the voltage regulator
- 3Start the generator set
- 4With the generator set running, apply 12VDC from a wet cell battery (automotive type) to the F1 and F2 exciter winding leads for 1 second
- 5Stop the generator set and reconnect the F1 and F2 leads to the voltage regulator