F2 (5A-T)
UnclassifiedElectrical
What This Code Means
Abnormal low voltage, charger is operating; Battery is discharged, but the charger has power and is operating; Charger not operating
Possible Causes
- •Battery completely discharged
- •Charger operating at current limit
- •Blown fuse
- •No power to the charger
Suggested Actions
- 1Disconnect the battery and verify that the charger output is 13.2 VDC
- 2Reconnect the charger and allow time for the battery to recharge
- 3Battery voltage should rise gradually
- 4Test the battery
- 5Check the 5-amp fuse F2 (5A-T) inside the battery charger and replace if necessary
- 6Check inline fuse F4 and replace if necessary
- 7Check the power supply to the charger
- 8Check the upstream circuit breakers and fuses
- 9Check fuse FS (1A-T) inside the battery charger