F2
What This Code Means
Emergency Stop activated; Common Fault / Prealarm; Blown F1 fuse (remote annunciator: 3amp); Blown F2 fuse (controller: 3amp); Blown F3 fuse (engine and accessories: 15amp); Engine will not crank; Controller LED4 is not lit; Controller LED4 is not lit after placing test jumper between TB1-1 and TB1-1A; Controller LED4 is lit; Controller LED2 and LED3 do not light with generator master switch in RUN position; Controller LED2 and LED3 light with generator master switch in RUN position; Lamps do not light when pressing lamptest button; Generator failure to stop; Engine fault protection; Generator failure to start; Generator failure to run; Incorrect AC voltage or current readings; Inability to select AC output for measurement; Incorrect generator voltage regulation; Unstable generator output voltage; Fault shutdown; Remote annunciator not functioning; Controller not functioning; Speed sensor not functioning; Lamp circuit board not functioning; Engine/starting circuitry not functioning; Ac
Possible Causes
- •AOP activated
- •AUX activated
- •AWT activated
- •Battery Charger Fault activated
- •Battery connections reversed
- •Defective audio/visual alarm
- •Defective dry contact kit
- •Defective engine electrical components
- •Defective overvoltage board
- •Defective panel lamps, engine gauges
- •HWT activated
- •LOP activated
- •Low Battery activated
- •Low Fuel activated
- •OC activated
- •OS activated
- •Remaining accessories connected to TB1-42A
- •Remote switch activated
- •Shorted DC supply to indicator panel
- •Shorted controller circuit board
Suggested Actions
- 1Charge battery and attempt restart
- 2Check P1 connector/harness
- 3Check engine start circuit (P1 harness, starter, solenoid, battery connections)
- 4Check for DC voltage at Fuse F2 (3amp)
- 5Check fuse
- 6Check if battery connections are loose or reversed
- 7If fuse blows again, refer to Fuses earlier in this section
- 8Inspect and repair P3/P4 harness and connections
- 9Isolate and repair or replace defective component.
- 10Place test jumper between TB1-1 and TB1-1A
- 11Refer to Fuses earlier in this section if fuse blows again
- 12Remove test jumper before proceeding
- 13Repair/replace defective emergency stop switch (controller or remote)
- 14Repair/replace defective emergencystop switch (controller or remote)
- 15Replace circuit board
- 16Replace defective indicator panel circuit board
- 17Replace fuse
- 18Replace fuse and resume operation. If fuse blows again, use chart to identify faulty component(s).
- 19Reset air damper on 200-1600kW Detroit Diesel models only
- 20Reset emergency stop switch (controller or remote)