CONCHECKFAIL

UnclassifiedElectrical

What This Code Means

Incompatible model numbers for paralleled generators; Incorrect configuration of one of the generators; Different generator types; System voltage of the two generators intended to be paralleled is not the same; Generators will not be allowed to start; Failure to Auto-Discover APM connections; APM connection auto-discovery is not complete; Generator does not know which contactor is connected to it

Possible Causes

  • Different generator types.
  • Generators not yet started in RUN with other generator in OFF.
  • Incorrect configuration of one of the generators.
  • Intermittent connections on RBUS network wiring.
  • One of the two generators is incorrectly configured.
  • The system voltage of the two generators intended to be paralleled is not the same.
  • Two generators intended to be paralleled have incompatible model numbers.
  • Wires 9A and 9B crossed between the generators
  • Wires 9A and 9B crossed between the generators.
  • Wires 9A or 9B not connected

Suggested Actions

  1. 1Check for crossed wires 9A and 9B between generators.
  2. 2Connect wires 9A or 9B
  3. 3Correct crossed wires 9A and 9B between the generators
  4. 4Correct wire connections by uncrossing wires 9A and 9B
  5. 5Ensure the system voltage of both generators is the same.
  6. 6Ensure wires 9A or 9B are connected.
  7. 7Place the other generator in OFF and this generator in RUN to activate auto-discovery.
  8. 8See the APM instruction sheet for instructions to perform the auto-discovery procedure.
  9. 9The paralleled generator sets must be the same kW model. (i.e. two 14 kW or two 20 kW models.)