CFGMODELNUM
UnclassifiedElectrical
What This Code Means
Incompatible model numbers for paralleled generators; Incorrect configuration of one of the generators; Different generator types; System voltage of the two generators intended to be paralleled is not the same; Generators will not be allowed to start; Failure to Auto-Discover APM connections; APM connection auto-discovery is not complete; Generator does not know which contactor is connected to it
Possible Causes
- •Different generator types
- •Different generator types.
- •Generators are not the same kW model
- •Generators not yet started in RUN with other generator in OFF.
- •Incorrect configuration of one of the generators
- •Incorrect configuration of one of the generators.
- •Intermittent connections on RBUS network wiring.
- •One of the two generators is incorrectly configured.
- •The system voltage of the two generators intended to be paralleled is not the same.
- •The two generators that are intended to be paralleled have incompatible model numbers
- •Two generators intended to be paralleled have incompatible model numbers.
- •Wires 9A and 9B crossed between the generators.
- •Wires 9A or 9B not connected
Suggested Actions
- 1Check for crossed wires 9A and 9B between generators.
- 2Contact an authorized dealer for paralleling system installation, startup, troubleshooting, or service
- 3Contact an authorized distributor or dealer for paralleling system troubleshooting or service
- 4Correct the configuration of the generators
- 5Ensure paralleled generator sets are the same kW model (e.g., two 14 kW, two 20 kW, or two 26 kW models)
- 6Ensure the system voltage of both generators is the same.
- 7Ensure wires 9A or 9B are connected.
- 8Place the other generator in OFF and this generator in RUN to activate auto-discovery.
- 9See the APM instruction sheet for instructions to perform the auto-discovery procedure.
- 10The paralleled generator sets must be the same kW model (i.e. two 14 kW or two 20 kW models)
- 11The paralleled generator sets must be the same kW model. (i.e. two 14 kW or two 20 kW models.)