81 O
What This Code Means
Generator set is operating at a potentially damaging frequency level; Over frequency shutdown; Over frequency warning; Generator set shutdown; Output voltage on any phase exceeds preset values; Voltage on any phase drops below preset value; Generator set output frequency cannot be maintained; Generator set warning; Generator set operating at potentially damaging frequency level; Instantaneous tripping (50mS response to turn off AVR excitation/shutdown generator set); 1-Phase short circuit; 2-Phase short circuit; 3-Phase short circuit; Output voltage on any phase exceeds preset values (105-125% of nominal); Voltage on any phase has dropped below a preset value (50-95% of reference); Generator set output frequency cannot be maintained (2-10 Hz below reference governor set point); 3-Phase short circuit (thermal damage); Voltage on any phase has dropped below a preset value; Over frequency shutdown/warning
Possible Causes
- •Generator frequency exceeds nominal governor set point by 2-10 Hz for a 1-20 second time delay
- •Output voltage on any phase exceeds preset threshold (105-125% of nominal voltage)
- •Voltage on any phase drops below preset threshold (50-95% of reference voltage)
- •Generator set output frequency drops below reference governor set point (2-10 Hz below)
- •Generator set is operating at a potentially damaging frequency level
- •AmpSentry Maintenance Mode (AMM) is active for arc flash reduction when personnel are near the generator set
- •Fault conditions in the generator set or in the load
- •Generator frequency exceeds nominal governor set point (by 2-10 Hz)
- •High AC voltage
- •Low AC voltage
- •Under frequency
- •Over frequency
- •Short circuit
- •Voltage on any phase exceeds preset threshold (adjustable from 105 - 125% of nominal voltage)
- •Voltage on any phase drops below preset threshold (adjustable over a range of 50 - 95% of reference voltage)
- •Output frequency drops below reference governor set point by adjustable range of 2 - 10 Hz
- •Generator set is operating above nominal governor set point by adjustable range of 2 - 10 Hz
- •Generator set operating at 2 - 10 Hz above nominal governor set point
Suggested Actions
- 1Adjust over frequency settings (adjustable from 2-10 Hz above nominal governor set point for a 1-20 second time delay)
- 2Adjust high AC voltage threshold setting (adjustable from 105-125% of nominal voltage)
- 3Adjust time delay (adjustable from 0.1-10 seconds)
- 4Adjust low AC voltage threshold setting (adjustable from 50-95% of reference voltage)
- 5Adjust time delay (adjustable from 2-20 seconds)
- 6Adjust under frequency threshold setting (adjustable from 2-10 Hz below reference governor set point)
- 7Adjust time delay (adjustable from 5-20 seconds)
- 8Allow downstream protective devices to clear fault conditions using single and three phase fault current regulation
- 9Rely on thermal damage curve (3-Phase short) or fixed timer (2 seconds for 1-Phase short, 5 seconds for 2-Phase short) to protect the alternator
- 10Adjust over frequency settings (2-10 Hz above nominal governor set point)
- 11Adjust time delay settings (1-20 seconds)
- 12Shutdown generator set
- 13Turn off AVR excitation
- 14Warning
- 15Instantaneous tripping (if AmpSentry Maintenance Mode is active)
- 16Adjust over frequency settings (adjustable from 2 - 10 Hz above nominal governor set point for a 1 - 20 second time delay)