81 U

UnclassifiedElectrical

What This Code Means

Generator set shutdown; Output voltage on any phase exceeds preset values; Voltage on any phase drops below preset value; Generator set output frequency cannot be maintained; Generator set warning; Generator set operating at potentially damaging frequency level; Instantaneous tripping (50mS response to turn off AVR excitation/shutdown generator set); 1-Phase short circuit; 2-Phase short circuit; 3-Phase short circuit; Output voltage on any phase exceeds preset values (105-125% of nominal); Voltage on any phase has dropped below a preset value (50-95% of reference); Generator set output frequency cannot be maintained (2-10 Hz below reference governor set point); Generator set is operating at a potentially damaging frequency level; 3-Phase short circuit (thermal damage); Shutdown of generator set; Voltage on any phase has dropped below a preset value

Possible Causes

  • Output voltage on any phase exceeds preset threshold (105-125% of nominal voltage)
  • Voltage on any phase drops below preset threshold (50-95% of reference voltage)
  • Generator set output frequency drops below reference governor set point (2-10 Hz below)
  • Generator set is operating at a potentially damaging frequency level
  • AmpSentry Maintenance Mode (AMM) is active for arc flash reduction when personnel are near the generator set
  • Fault conditions in the generator set or in the load
  • High AC voltage
  • Low AC voltage
  • Under frequency
  • Over frequency
  • Short circuit
  • Output frequency drops 2-10 Hz below nominal governor set point for a 5-20 second time delay
  • Generator set frequency rises 2-10 Hz above nominal governor set point for a 1-20 second time delay
  • Loss of voltage sensing inputs to the control
  • Field overload condition
  • Voltage on any phase exceeds preset threshold (adjustable from 105 - 125% of nominal voltage)
  • Voltage on any phase drops below preset threshold (adjustable over a range of 50 - 95% of reference voltage)
  • Output frequency drops below reference governor set point by adjustable range of 2 - 10 Hz
  • Generator set is operating above nominal governor set point by adjustable range of 2 - 10 Hz

Suggested Actions

  1. 1Adjust high AC voltage threshold setting (adjustable from 105-125% of nominal voltage)
  2. 2Adjust time delay (adjustable from 0.1-10 seconds)
  3. 3Adjust low AC voltage threshold setting (adjustable from 50-95% of reference voltage)
  4. 4Adjust time delay (adjustable from 2-20 seconds)
  5. 5Adjust under frequency threshold setting (adjustable from 2-10 Hz below reference governor set point)
  6. 6Adjust time delay (adjustable from 5-20 seconds)
  7. 7Allow downstream protective devices to clear fault conditions using single and three phase fault current regulation
  8. 8Rely on thermal damage curve (3-Phase short) or fixed timer (2 seconds for 1-Phase short, 5 seconds for 2-Phase short) to protect the alternator
  9. 9Shutdown generator set
  10. 10Turn off AVR excitation
  11. 11Warning
  12. 12Instantaneous tripping (if AmpSentry Maintenance Mode is active)