81 U
What This Code Means
Generator set shutdown; Output voltage on any phase exceeds preset values; Voltage on any phase drops below preset value; Generator set output frequency cannot be maintained; Generator set warning; Generator set operating at potentially damaging frequency level; Instantaneous tripping (50mS response to turn off AVR excitation/shutdown generator set); 1-Phase short circuit; 2-Phase short circuit; 3-Phase short circuit; Output voltage on any phase exceeds preset values (105-125% of nominal); Voltage on any phase has dropped below a preset value (50-95% of reference); Generator set output frequency cannot be maintained (2-10 Hz below reference governor set point); Generator set is operating at a potentially damaging frequency level; 3-Phase short circuit (thermal damage); Shutdown of generator set; Voltage on any phase has dropped below a preset value
Possible Causes
- •Output voltage on any phase exceeds preset threshold (105-125% of nominal voltage)
- •Voltage on any phase drops below preset threshold (50-95% of reference voltage)
- •Generator set output frequency drops below reference governor set point (2-10 Hz below)
- •Generator set is operating at a potentially damaging frequency level
- •AmpSentry Maintenance Mode (AMM) is active for arc flash reduction when personnel are near the generator set
- •Fault conditions in the generator set or in the load
- •High AC voltage
- •Low AC voltage
- •Under frequency
- •Over frequency
- •Short circuit
- •Output frequency drops 2-10 Hz below nominal governor set point for a 5-20 second time delay
- •Generator set frequency rises 2-10 Hz above nominal governor set point for a 1-20 second time delay
- •Loss of voltage sensing inputs to the control
- •Field overload condition
- •Voltage on any phase exceeds preset threshold (adjustable from 105 - 125% of nominal voltage)
- •Voltage on any phase drops below preset threshold (adjustable over a range of 50 - 95% of reference voltage)
- •Output frequency drops below reference governor set point by adjustable range of 2 - 10 Hz
- •Generator set is operating above nominal governor set point by adjustable range of 2 - 10 Hz
Suggested Actions
- 1Adjust high AC voltage threshold setting (adjustable from 105-125% of nominal voltage)
- 2Adjust time delay (adjustable from 0.1-10 seconds)
- 3Adjust low AC voltage threshold setting (adjustable from 50-95% of reference voltage)
- 4Adjust time delay (adjustable from 2-20 seconds)
- 5Adjust under frequency threshold setting (adjustable from 2-10 Hz below reference governor set point)
- 6Adjust time delay (adjustable from 5-20 seconds)
- 7Allow downstream protective devices to clear fault conditions using single and three phase fault current regulation
- 8Rely on thermal damage curve (3-Phase short) or fixed timer (2 seconds for 1-Phase short, 5 seconds for 2-Phase short) to protect the alternator
- 9Shutdown generator set
- 10Turn off AVR excitation
- 11Warning
- 12Instantaneous tripping (if AmpSentry Maintenance Mode is active)