427

UnclassifiedLubrication

What This Code Means

Low oil rifle pressure; Engine shutdown; Communication between the engine control (ECM) and the PCC is severed; CAN Data Link Degraded warning; Battery voltage is below 24 VDC and approaching low level; Unpredictable equipment operation; Low Battery 1 Voltage warning; Battery voltage to the control is approaching high level (exceeding 32 VDC); Potential damage to the control; High Battery 1 Voltage warning

Possible Causes

  • •Active E-Stop button
  • •CAN Datalink failure
  • •Communication between the engine control (ECM) and the generator set control is severed
  • •Control failed to receive engine speed from ECM during cranking
  • •Datalink fault
  • •Defective Datalink Harness Assembly
  • •Defective datalink harness connection or open circuit
  • •Dirty battery terminals or loose connections
  • •Discharged or defective battery
  • •Fault with the control, speed sensing, or starting system
  • •Important data lost between PCC control and engine control module
  • •Incorrect battery charge float level
  • •Low electrolyte level
  • •Low oil level
  • •O pressed on control during genset operation
  • •Oil system issues (lines or filters)
  • •Power Removed From ECM (Keyswitch) During Genset Operation
  • •The ECM is powered down
  • •The networking harness is defective

Suggested Actions

  1. 1Allow the engine to cool down completely before proceeding
  2. 2Allow the engine to cool down completely before proceeding with checks
  3. 3Check for 60 Ohms resistance between J11-20 and J11-19; repair the harness if resistance is incorrect
  4. 4Check for a defective datalink harness connection or open circuit
  5. 5Check the battery charge float level and lower float level if applicable
  6. 6Check the datalink between the ECM and the GCS for opens or shorts between J11-20 (CANH), J11-19 (CANL), and J11-17 (CAN Shield)
  7. 7Check the electrolyte level, top up and re-charge (if applicable)
  8. 8Check the oil level, lines and filters
  9. 9Clean battery terminals and tighten all connections
  10. 10Clean the battery terminals and tighten all connections
  11. 11Consult the engine service manual for MPU diagnostic
  12. 12Ensure the E-Stop button is not active
  13. 13If B+ doesn't exist, repair the defective harness
  14. 14If GND doesn't exist on the relay coil, check for GND on P11-21 (Keyswitch LS Out). If GND exists, repair the defective harness
  15. 15If GND on P11-21 does not exist, replace the defective Base board
  16. 16If the engine can be stopped, allow the engine to cool down completely before proceeding
  17. 17Inspect the datalink harness and connector pins from J11-20 to J1939 HIGH (J26-11)
  18. 18Recharge or replace battery
  19. 19Refer to Fault Code 427 or 781
  20. 20Replenish oil level if low
  21. 21Reset control by pressing Fault Reset button with O/Manual/Auto switch in O (off) position
  22. 22Reset the Local/Remote Emergency Stop
  23. 23Reset the control and restart after locating and correcting the problem
  24. 24See Fault Code 427 or 781 for datalink health diagnostic