201
UnclassifiedGeneral
What This Code Means
Invalid output channel; No chargers assigned to output channel; Charger has failed; Charger has lost SENSbus data communication; Charger has incorrect channel setting
Possible Causes
- •Charger has failed
- •Charger has lost SENSbus data communication
- •Chargers must be set to use a valid output channel setting
- •Damaged SENSbus data cables
- •Disconnected SENSbus data cables
- •Every enabled output channel must have at least one charger assigned to it
- •Incorrect channel setting
- •Output channel setting is incorrect
Suggested Actions
- 1Check for a charger that has failed (indicated by its LED status)
- 2Check for a charger that has failed (indicated by its LED status).
- 3Check for disconnected or damaged SENSbus data cables
- 4Check for disconnected or damaged SENSbus data cables.
- 5Disable the output channel if it is not to be used by using the keypad 'DC Output #' setting in the 'DC -> Advanced Settings' menu or the setup utility
- 6Enable the channel using the keypad 'DC Output #' selection in the 'DC -> Advanced Settings' menu or the setup utility
- 7If the output channel is not to be used, disable it by using the keypad 'DC Output #' setting in the 'DC -> Advanced Settings' menu or the setup utility.
- 8Reassign the charger to match its actual output channel connection using the setup utility
- 9Use output A for single output units
Related Stored Energy Systems LLC Fault Codes
ASK RUDY ABOUT THIS FAULT
Get a diagnosis walkthrough for 201 on your specific Stored Energy Systems LLC unit — cited to the OEM manual, not a forum guess.
TRY IT FREE