196

UnclassifiedCooling

What This Code Means

Engine has overheated; Intake manifold temperature has risen above the shutdown trip point; Engine coolant level has fallen below the trip point

Possible Causes

  • •Coolant leakage
  • •High ambient temperature
  • •Large load
  • •Radiator sensor detected coolant level out of range (OOR), low
  • •The engine controller has sensed a fault condition and is broadcasting the fault message

Suggested Actions

  1. 1Check coolant level and replenish if low
  2. 2Consult the engine service manual
  3. 3If the engine can be stopped, allow the engine to cool down completely before proceeding
  4. 4If the generator is powering critical loads and cannot be shut down, wait until the next shutdown period
  5. 5Look for possible coolant leakage points and repair if necessary
  6. 6Reset the control and restart after locating and correcting the problem
  7. 7Review fault code 151 correction list for other possible causes