What This Code Means

VSCF IGBT Overtemp.; IGBT temperature greater than 85 deg. C; Insufficient air flow around unit

Possible Causes

  • •Ambient temperature above 50C
  • •Insufficient air flow around unit
  • •The AVR air filter needs replacing
  • •The BIG fan is not running
  • •The air path is blocked, either intake or exhaust or through the unit
  • •The engine is running too hot
  • •There is an air leak in the AVR enclosure

Suggested Actions

  1. 1Check AVR Air flow for restriction
  2. 2Check Generator air vents for restriction
  3. 3Check for Overload conditions
  4. 4Perform Auxiliary Power Supply test
  5. 5Perform Large Fan test
  6. 6Perform Small Fan and Large Fan test
  7. 7Perform Small fan test