1001

UnclassifiedCooling

What This Code Means

External display board is not able to communicate with main board; Main board does not see communication from display board; Overcrank; Low to no fuel pressure while cranking; Overspeed (Over 72 Hz for three seconds); Throttle stuck open; Overspeed (Over 75 Hz for one second); Total loss of control; High temperature (Coolant temp greater than 246 ºF (119 ºC) for 1 second); Overcrank alarm; Overspeed (Over 72 Hz for three seconds with the throttle stuck open); Overspeed (Over 75 Hz for one second with the throttle stuck open, total loss of control); Low oil pressure while running; Configuration Mismatch

Possible Causes

  • Internal Harness Loop Broken (internal to the display board)
  • Internal harness connecting external display board to main board has become disconnected
  • Engine/Starter Problem
  • No Fuel Pressure
  • Stuck throttle
  • Air Flow Impeded / Flow Issue
  • Flow issue
  • Internal harness loop broken (external display board)
  • Low to no fuel pressure while cranking
  • Check the oil level
  • Air flow impeded
  • Voltage configuration set in controller does not match voltage configuration for installed Voltage Configuration Cartridge (VCC).

Suggested Actions

  1. 1Fuel pressure has to be measured as low for at least 1200 ms before the overcrank alarm is set.
  2. 2Check the inlet/outlet for debris.
  3. 3Check coolant sensor circuit for proper operation.
  4. 4Check the inlet/outlet for debris
  5. 5Check coolant sensor circuit for proper operation

Related Generac Fault Codes