005349

UnclassifiedGeneral

What This Code Means

Minimal output at the breaker; DMM indicated INFINITY or a high resistance (in Test 11 Results - Step 3); DMM indicated Infinity (in Step 3); DMM indicated Infinity or high resistance (in Step 6); DMM indicated Infinity or high resistance (in Step 7); Fault is not corrected; DMM not within +/- 10% of the correct stator value (in Step 3)

Possible Causes

  • Regulator does not receive AC sensing voltage
  • Open wire in Wire 2 or Wire 6 from the TB1 terminal block to the stator
  • Integrity of Wires 2 and 6 from the TB1 terminal block to the stator needs verification
  • Fault with Wire 2
  • Fault with Wire 6
  • Potential issue with controller and DMM readings

Suggested Actions

  1. 1Test AC sensing circuit
  2. 2If DMM indicates INFINITY between TB1 Wire SA/11/S1/S15 and AC sensing input to control board, repair or replace the wire between SA and the control board.
  3. 3If DMM indicates INFINITY between TB1 Wire SB/44/S3/S16 and AC sensing input to control board, repair or replace the wire between SB and the control board.
  4. 4Repair or replace open wire(s)
  5. 5Replace the stator (if no other fault is found)
  6. 6Verify the integrity of Wires 2 and 6 from the TB1 terminal block to the stator.
  7. 7If an open wire is found, repair or replace.
  8. 8If no other fault is found, replace the stator.
  9. 9Repair or replace Wire 2
  10. 10Repair or replace Wire 6
  11. 11Proceed back to the flowchart.
  12. 12Verify controller and DMM readings.