005347
UnclassifiedGeneral
What This Code Means
DMM indicated INFINITY or a high resistance (in Test 11 Results - Step 3); DMM indicated Infinity (in Step 3); DMM indicated Infinity or high resistance (in Step 6); DMM indicated Infinity or high resistance (in Step 7); Fault is not corrected; DMM not within +/- 10% of the correct stator value (in Step 3)
Possible Causes
- •Open wire in Wire 2 or Wire 6 from the TB1 terminal block to the stator
- •Integrity of Wires 2 and 6 from the TB1 terminal block to the stator needs verification
- •Fault with Wire 2
- •Fault with Wire 6
- •Potential issue with controller and DMM readings
Suggested Actions
- 1Repair or replace open wire(s)
- 2Replace the stator (if no other fault is found)
- 3Verify the integrity of Wires 2 and 6 from the TB1 terminal block to the stator.
- 4If an open wire is found, repair or replace.
- 5If no other fault is found, replace the stator.
- 6Repair or replace Wire 2
- 7Repair or replace Wire 6
- 8Proceed back to the flowchart.
- 9Verify controller and DMM readings.
Related Generac Fault Codes