005347

UnclassifiedGeneral

What This Code Means

DMM indicated INFINITY or a high resistance (in Test 11 Results - Step 3); DMM indicated Infinity (in Step 3); DMM indicated Infinity or high resistance (in Step 6); DMM indicated Infinity or high resistance (in Step 7); Fault is not corrected; DMM not within +/- 10% of the correct stator value (in Step 3)

Possible Causes

  • Open wire in Wire 2 or Wire 6 from the TB1 terminal block to the stator
  • Integrity of Wires 2 and 6 from the TB1 terminal block to the stator needs verification
  • Fault with Wire 2
  • Fault with Wire 6
  • Potential issue with controller and DMM readings

Suggested Actions

  1. 1Repair or replace open wire(s)
  2. 2Replace the stator (if no other fault is found)
  3. 3Verify the integrity of Wires 2 and 6 from the TB1 terminal block to the stator.
  4. 4If an open wire is found, repair or replace.
  5. 5If no other fault is found, replace the stator.
  6. 6Repair or replace Wire 2
  7. 7Repair or replace Wire 6
  8. 8Proceed back to the flowchart.
  9. 9Verify controller and DMM readings.