UNDERSPEED ALARM
UnclassifiedSpeed
What This Code Means
Pick up calculation is not available; Engine rotation speed is calculated through the genset frequency instead of the pick up; Overspeed alarm active; Immediate engine stop; Underspeed alarm active; Stop with engine cooling; Overload alarm active
Possible Causes
- •The number of teeth of the gear is set to 0
- •Rotation speed of the engine ring gear exceeds the maximum limits (Thresholds table parameter 11) during the stabilization time (alarms table parameter 23)
- •Rotation speed of the engine ring gear is under the programmed minimum limits (Thresholds table parameter 12) during the stabilization time (alarms table parameter 26)
- •Effective amperage value in any phase is superior to the maximum programmed overload limit (Thresholds table parameter 7) but under the maximum limit of short-circuit (Thresholds table parameter 8)
Suggested Actions
- 1Introduce the number of teeth of the gear in Thresholds table parameter 24 to activate the pick up calculation
Related Himoinsa Fault Codes