SYNCHRONIZER OUTPUT LIMIT WARNING

UnclassifiedElectrical

What This Code Means

Permissive close is not allowed; Permissive conditions for close are not met; Synchronizing continues but normal operation cannot occur; SYNC1320 master synchronizer drive on the load share lines reaches its maximum limit; Synchronizer cannot reach the desired voltage or frequency level; Permissive close is removed

Possible Causes

  • •Any of the permissive criteria fall outside of the specified window
  • •Phase rotation of the Utility bus does not match the phase rotation of the generator bus
  • •SYNC1320 master synchronizer is trying to match voltage or frequency and cannot reach the desired level
  • •Utility source is unavailable
  • •Generator source is unavailable
  • •Utility and generator phase rotation are not the same
  • •The highest difference of all the generator phase voltages minus the utility phases is equal to or greater than the voltage window
  • •The phase difference is equal to or greater than the phase window, or it is not decreasing
  • •The frequency difference between the sources is equal to or greater than the frequency window
  • •Permissive conditions are not met for the duration of the time window

Suggested Actions

  1. 1Reset the fault before attempting normal operation