SYNCHRONIZER OUTPUT LIMIT WARNING

UnclassifiedElectrical

What This Code Means

Permissive close is not allowed; Permissive conditions for close are not met; Synchronizing continues but normal operation cannot occur; SYNC1320 master synchronizer drive on the load share lines reaches its maximum limit; Synchronizer cannot reach the desired voltage or frequency level; Permissive close is removed

Possible Causes

  • Any of the permissive criteria fall outside of the specified window
  • Phase rotation of the Utility bus does not match the phase rotation of the generator bus
  • SYNC1320 master synchronizer is trying to match voltage or frequency and cannot reach the desired level
  • Utility source is unavailable
  • Generator source is unavailable
  • Utility and generator phase rotation are not the same
  • The highest difference of all the generator phase voltages minus the utility phases is equal to or greater than the voltage window
  • The phase difference is equal to or greater than the phase window, or it is not decreasing
  • The frequency difference between the sources is equal to or greater than the frequency window
  • Permissive conditions are not met for the duration of the time window

Suggested Actions

  1. 1Reset the fault before attempting normal operation

ASK RUDY ABOUT THIS FAULT

Get a diagnosis walkthrough for SYNCHRONIZER OUTPUT LIMIT WARNING on your specific Cummins unit — cited to the OEM manual, not a forum guess.

TRY IT FREE