S/N WARNING

UnclassifiedGeneral

What This Code Means

S/N WARNING is displayed; GENSET S/N WARNING display appears

Possible Causes

  • •GENSET SERIAL NO. and SERIAL NO. do not match

Suggested Actions

  1. 1Go to Menu 20, Factory Setup
  2. 2Arrow down to the SERIAL NO. display
  3. 3Enter the serial number of the generator set using data recorded from the old controller or as shown on the generator set nameplate (enter a leading zero if the serial number is six digits)
  4. 4Press the ENTER key

ASK RUDY ABOUT THIS FAULT

Get a diagnosis walkthrough for S/N WARNING on your specific Rehlko unit — cited to the OEM manual, not a forum guess.

GET THE ANSWER

Free account required — we'll bring your question with you.