OVERCRANK

UnclassifiedSpeed

What This Code Means

Alarm horn sounds; Not in AUTO lamp lights; Generator set slows to 750rpm (25 Hz) and recranks before returning to rated speed; Engine shuts down on an overcrank fault

Possible Causes

  • Engine ECM limits the crank cycle
  • Engine cranks up to 45 seconds continuously or 75 seconds cyclically before shutting down.
  • Engine does not start after 45 seconds of continuous cranking
  • Engine does not start after 75 seconds of cyclic cranking
  • Engine fails to start within the maximum continuous (45 seconds) or cyclic (75 seconds) cranking limit
  • FASTCHECK engine switch is not moved from CRANK to RUN while the controller is causing the engine to crank
  • Generator set fails to start after three crank cycles (15 seconds crank and 15 seconds off)
  • Generator set fails to start after two crank cycles with 3 starting attempts during each cycle (applicable to 20 and 26 kW Models with RDC2.4 v 1.4.4 or later)
  • Generator set master switch is not in the AUTO position
  • Generator set master switch was momentarily placed in the OFF/RESET position and then returned to the RUN position
  • Speed sensor signal is absent for longer than one second
  • Starter or engine does not turn (locked rotor) after 15 seconds

Suggested Actions

  1. 1If circuit boards are equipped with DIP switches, select cranking using a DIP switch.
  2. 2Move FASTCHECK engine switch to RUN
  3. 3Move the generator set master switch to the AUTO position
  4. 4Refer to Section 2.3.1, Microprocessor Controller Features, for instructions on selecting cyclic or continuous cranking mode on the controller circuit board terminal strip.
  5. 5See the Faults section of the manual
  6. 6This is a normal operation for transient start/stop. No specific resolution mentioned beyond the description of the behavior.