OVERCRANK
UnclassifiedSpeed
What This Code Means
Generator fails to start after 30 seconds; Fault light illuminated; LED 1 lights (K1 relay energized); LED 5 lights (K5 relay energized); Power removed from wire #70; Ground held to remote start lead wire #4
Possible Causes
- •Engine ECM limits the crank cycle
- •Engine cranks up to 45 seconds continuously or 75 seconds cyclically before shutting down.
- •Engine does not start after 45 seconds of continuous cranking
- •Engine does not start after 75 seconds of cyclic cranking
- •Engine fails to start after 70 seconds of cyclic cranking (20 seconds crank, 5 seconds rest)
- •Engine fails to start within 30 seconds total cyclic time
- •Engine fails to start within the maximum continuous (45 seconds) or cyclic (75 seconds) cranking limit
- •Engine fails to start within total allocated cyclic time (30 seconds)
- •Engine fails to start within total cyclic time (30 seconds)
- •Engine mechanical lock or starter malfunction
- •FASTCHECK engine switch is not moved from CRANK to RUN while the controller is causing the engine to crank
- •Faulty speed sensor
- •Faulty speed sensor and related circuitry
- •Faulty speed sensor or related circuitry
- •Faulty speed sensor related circuitry
- •Generator fails to start after 30 seconds
- •Generator set fails to start after three crank cycles (15 seconds crank and 15 seconds off)
- •Generator set fails to start after two crank cycles with 3 starting attempts during each cycle (applicable to 20 and 26 kW Models with RDC2.4 v 1.4.4 or later)
- •Generator set master switch is not in the AUTO position
- •Generator set master switch was momentarily placed in the OFF/RESET position and then returned to the RUN position
- •Overcrank condition
- •Speed sensor signal is absent for longer than one second
- •Starter or engine does not turn (locked rotor) after 15 seconds
- •Échec de démarrage du groupe électrogène après trois tentatives consécutives (trois cycles de 15 secondes de lancement et 15 secondes d'arrêt)
- •Échec de démarrage du moteur après trois cycles (3 cycles de 15 secondes de lancement et 15 secondes d'arrêt)
- •Échec du démarrage du groupe électrogène après 3 cycles de 15 secondes de lancement et 15 secondes d'arrêt
Suggested Actions
- 1Check for operating voltage between TB1-42A (+) and TB1-12 (-)
- 2Check for operating voltage between TB1-42A(+) and TB1-12(-)
- 3Check the speed sensor and related circuitry
- 4If circuit boards are equipped with DIP switches, select cranking using a DIP switch.
- 5Move FASTCHECK engine switch to OFF
- 6Move FASTCHECK engine switch to RUN
- 7Move generator set master switch to OFF and then to RUN
- 8Move the generator set master switch to the AUTO position
- 9Perform Controller Speed Sensor Circuitry test using FASTCHECK engine switch
- 10Perform Speed Sensor Test in Section 7—Component Testing and Adjustment
- 11Place selector switch in 'Reset/Off' position prior to attempting another start cycle
- 12Place selector switch in the "reset/off" position prior to attempting another start cycle
- 13Place the selector switch in the 'reset/off' position prior to attempting another start cycle
- 14Refer to Section 2.3.1, Microprocessor Controller Features, for instructions on selecting cyclic or continuous cranking mode on the controller circuit board terminal strip.
- 15Refer to Section 5.13, Magnetic Pickup to test speed sensor output
- 16Refer to Section 7, Speed Sensor to test speed sensor output
- 17Se reporter à la Section 2.5
- 18See Speed Sensor Test in Section 7—Component Testing and Adjustment
- 19See the Faults section of the manual
- 20This is a normal operation for transient start/stop. No specific resolution mentioned beyond the description of the behavior.
- 21Verify IGN., CRK., and REG. lamps on FASTCHECK light for approximately 5 seconds, go out, and relight 5 seconds later for 5 seconds (15 seconds total elapsed time)
- 22Verify operation of the overcrank circuit