OVERCRANK

UnclassifiedSpeed

What This Code Means

Generator fails to start after 30 seconds; Fault light illuminated; LED 1 lights (K1 relay energized); LED 5 lights (K5 relay energized); Power removed from wire #70; Ground held to remote start lead wire #4

Possible Causes

  • •Engine ECM limits the crank cycle
  • •Engine cranks up to 45 seconds continuously or 75 seconds cyclically before shutting down.
  • •Engine does not start after 45 seconds of continuous cranking
  • •Engine does not start after 75 seconds of cyclic cranking
  • •Engine fails to start after 70 seconds of cyclic cranking (20 seconds crank, 5 seconds rest)
  • •Engine fails to start within 30 seconds total cyclic time
  • •Engine fails to start within the maximum continuous (45 seconds) or cyclic (75 seconds) cranking limit
  • •Engine fails to start within total allocated cyclic time (30 seconds)
  • •Engine fails to start within total cyclic time (30 seconds)
  • •Engine mechanical lock or starter malfunction
  • •FASTCHECK engine switch is not moved from CRANK to RUN while the controller is causing the engine to crank
  • •Faulty speed sensor
  • •Faulty speed sensor and related circuitry
  • •Faulty speed sensor or related circuitry
  • •Faulty speed sensor related circuitry
  • •Generator fails to start after 30 seconds
  • •Generator set fails to start after three crank cycles (15 seconds crank and 15 seconds off)
  • •Generator set fails to start after two crank cycles with 3 starting attempts during each cycle (applicable to 20 and 26 kW Models with RDC2.4 v 1.4.4 or later)
  • •Generator set master switch is not in the AUTO position
  • •Generator set master switch was momentarily placed in the OFF/RESET position and then returned to the RUN position
  • •Overcrank condition
  • •Speed sensor signal is absent for longer than one second
  • •Starter or engine does not turn (locked rotor) after 15 seconds
  • •Échec de démarrage du groupe électrogène après trois tentatives consécutives (trois cycles de 15 secondes de lancement et 15 secondes d'arrêt)
  • •Échec de démarrage du moteur après trois cycles (3 cycles de 15 secondes de lancement et 15 secondes d'arrêt)
  • •Échec du démarrage du groupe électrogène après 3 cycles de 15 secondes de lancement et 15 secondes d'arrêt

Suggested Actions

  1. 1Check for operating voltage between TB1-42A (+) and TB1-12 (-)
  2. 2Check for operating voltage between TB1-42A(+) and TB1-12(-)
  3. 3Check the speed sensor and related circuitry
  4. 4If circuit boards are equipped with DIP switches, select cranking using a DIP switch.
  5. 5Move FASTCHECK engine switch to OFF
  6. 6Move FASTCHECK engine switch to RUN
  7. 7Move generator set master switch to OFF and then to RUN
  8. 8Move the generator set master switch to the AUTO position
  9. 9Perform Controller Speed Sensor Circuitry test using FASTCHECK engine switch
  10. 10Perform Speed Sensor Test in Section 7—Component Testing and Adjustment
  11. 11Place selector switch in 'Reset/Off' position prior to attempting another start cycle
  12. 12Place selector switch in the "reset/off" position prior to attempting another start cycle
  13. 13Place the selector switch in the 'reset/off' position prior to attempting another start cycle
  14. 14Refer to Section 2.3.1, Microprocessor Controller Features, for instructions on selecting cyclic or continuous cranking mode on the controller circuit board terminal strip.
  15. 15Refer to Section 5.13, Magnetic Pickup to test speed sensor output
  16. 16Refer to Section 7, Speed Sensor to test speed sensor output
  17. 17Se reporter à la Section 2.5
  18. 18See Speed Sensor Test in Section 7—Component Testing and Adjustment
  19. 19See the Faults section of the manual
  20. 20This is a normal operation for transient start/stop. No specific resolution mentioned beyond the description of the behavior.
  21. 21Verify IGN., CRK., and REG. lamps on FASTCHECK light for approximately 5 seconds, go out, and relight 5 seconds later for 5 seconds (15 seconds total elapsed time)
  22. 22Verify operation of the overcrank circuit