LED1
UnclassifiedSpeed
What This Code Means
Generator set shuts down when engine speed exceeds 3750 rpm
Possible Causes
- •Engine overspeed (exceeding 3750 rpm / 750 Hz)
- •Engine speed exceeds 3750 rpm
- •Frequency exceeds 750 Hz across terminals C and E on the AC side of the voltage rectifier
Suggested Actions
- 1Connect frequency meter across terminals C and E on the AC side of the voltage rectifier to test overspeed shutdown at 750 Hz
- 2Perform overspeed shutdown test
- 3Reset the controller by moving the master switch to the OFF position and then back to AUTO
Related Rehlko Fault Codes