OVERCRANK FAULT

UnclassifiedCooling

What This Code Means

Generator set does not start in three attempts; System shuts down on an overcrank fault; Exhaust leaks; Exhaust blockages; Insufficient cooling air flow; generator set does not start in three attempts; generator set does not start

Possible Causes

  • •AC output not obtained within 30 seconds
  • •Controller attempts to start the generator set three times without success.
  • •Corrosion in exhaust system components
  • •Cracks in exhaust system components
  • •Dirty air intake area.
  • •Engine fails to start within three crank cycles (15 seconds crank and 15 seconds off)
  • •Generator set does not start after three starting attempts (15 seconds crank and 15 seconds off)
  • •Generator set does not start during the designated crank cycles (3 starting attempts, a 45-second pause, followed by another 3 starting attempts)
  • •Generator set fails to start during the three 15-second crank cycles
  • •Generator set fails to start within three crank cycles (15 seconds crank and 15 seconds off)
  • •Lack of lubrication at startup
  • •Leaks in exhaust system components
  • •Loose exhaust system connections
  • •Obstructed exhaust outlet
  • •Obstructions in the operating area that could block the flow of cooling air.
  • •On 20 kW models with firmware v1.4.4 or later, generator set fails to start after two crank cycles of 3 starting attempts each (with a 45-second pause between cycles)
  • •Overcrank fault
  • •Rags, tools, or debris on or near the generator set.
  • •The controller attempts to start the generator set three times (three crank cycles, 15 seconds crank and 15 seconds off).
  • •Unprimed oil passage/engine lubrication system prior to initial startup
  • •failure to start after three crank cycles

Suggested Actions

  1. 1Add approximately 2 oz. of engine oil into the oil passage (using a syringe is recommended)
  2. 2Allow the controller to perform a 3-cycle cranking sequence (15 seconds crank / 15 seconds rest repeated 3 times) to build oil pressure without starting the engine until an overcrank fault occurs
  3. 3Apply new pipe sealant with Teflon (Loctite PST 592 or equivalent) to the threads
  4. 4Carefully remove any pipe sealant from the threads, taking care not to drop debris inside the opening
  5. 5Check for exhaust blockages.
  6. 6Check for obstructions that could block the flow of cooling air.
  7. 7Check for tight exhaust system connections.
  8. 8Check muffler condition.
  9. 9Check that the exhaust outlet is unobstructed.
  10. 10Check the oil level using the dipstick and ensure it is at the correct (full) level
  11. 11Clean off old pipe sealant from the threads without letting debris enter the oil port
  12. 12Disable the fuel supply by closing the manual fuel valve or disconnecting lead 70A from the fuel solenoid valve
  13. 13Disconnect the green oil pressure lead and remove the oil pressure switch from below the air cleaner
  14. 14Do not leave rags, tools, or debris on or near the generator set.
  15. 15Inject approximately 2 oz. of engine oil directly into the oil passage using a syringe
  16. 16Inspect exhaust system components for cracks, leaks, and corrosion.
  17. 17Keep the air intake area clean.
  18. 18Locate and disconnect the green electrical lead attached to the oil pressure switch and remove the switch
  19. 19Press RUN on the generator set controller to cycle/crank the engine (3 cycles of 15 seconds crank / 15 seconds rest) until the unit shuts down on an overcrank fault
  20. 20Press the OFF button on the generator set controller
  21. 21Pressing the OFF button during the crank cycle stops the cranking.
  22. 22Reconnect the green lead to the oil pressure switch
  23. 23Reconnect the green wire lead to the oil pressure switch terminal
  24. 24Reinstall the oil pressure switch and tighten to 10.7 Nm (95 in-lbs.)
  25. 25Reinstall the oil pressure switch using fresh pipe sealant with Teflon (Loctite PST 592 or equivalent), torquing to 10.7 N·m (95 in-lbs)
  26. 26Replace corroded or broken metal parts.
  27. 27See Section 2.6
  28. 28See Section 2.6 for information related to the overcrank fault.
  29. 29Shut off the fuel supply by closing the manual fuel valve or disconnecting lead 70A from the fuel solenoid valve
  30. 30System shuts down on overcrank fault.
  31. 31system shuts down on an overcrank fault