OVERCRANK FAULT
UnclassifiedCooling
What This Code Means
Generator set does not start in three attempts; System shuts down on an overcrank fault; Exhaust leaks; Exhaust blockages; Insufficient cooling air flow; generator set does not start in three attempts; generator set does not start
Possible Causes
- •AC output not obtained within 30 seconds
- •Controller attempts to start the generator set three times without success.
- •Corrosion in exhaust system components
- •Cracks in exhaust system components
- •Dirty air intake area.
- •Engine fails to start within three crank cycles (15 seconds crank and 15 seconds off)
- •Generator set does not start after three starting attempts (15 seconds crank and 15 seconds off)
- •Generator set does not start during the designated crank cycles (3 starting attempts, a 45-second pause, followed by another 3 starting attempts)
- •Generator set fails to start during the three 15-second crank cycles
- •Generator set fails to start within three crank cycles (15 seconds crank and 15 seconds off)
- •Lack of lubrication at startup
- •Leaks in exhaust system components
- •Loose exhaust system connections
- •Obstructed exhaust outlet
- •Obstructions in the operating area that could block the flow of cooling air.
- •On 20 kW models with firmware v1.4.4 or later, generator set fails to start after two crank cycles of 3 starting attempts each (with a 45-second pause between cycles)
- •Overcrank fault
- •Rags, tools, or debris on or near the generator set.
- •The controller attempts to start the generator set three times (three crank cycles, 15 seconds crank and 15 seconds off).
- •Unprimed oil passage/engine lubrication system prior to initial startup
- •failure to start after three crank cycles
Suggested Actions
- 1Add approximately 2 oz. of engine oil into the oil passage (using a syringe is recommended)
- 2Allow the controller to perform a 3-cycle cranking sequence (15 seconds crank / 15 seconds rest repeated 3 times) to build oil pressure without starting the engine until an overcrank fault occurs
- 3Apply new pipe sealant with Teflon (Loctite PST 592 or equivalent) to the threads
- 4Carefully remove any pipe sealant from the threads, taking care not to drop debris inside the opening
- 5Check for exhaust blockages.
- 6Check for obstructions that could block the flow of cooling air.
- 7Check for tight exhaust system connections.
- 8Check muffler condition.
- 9Check that the exhaust outlet is unobstructed.
- 10Check the oil level using the dipstick and ensure it is at the correct (full) level
- 11Clean off old pipe sealant from the threads without letting debris enter the oil port
- 12Disable the fuel supply by closing the manual fuel valve or disconnecting lead 70A from the fuel solenoid valve
- 13Disconnect the green oil pressure lead and remove the oil pressure switch from below the air cleaner
- 14Do not leave rags, tools, or debris on or near the generator set.
- 15Inject approximately 2 oz. of engine oil directly into the oil passage using a syringe
- 16Inspect exhaust system components for cracks, leaks, and corrosion.
- 17Keep the air intake area clean.
- 18Locate and disconnect the green electrical lead attached to the oil pressure switch and remove the switch
- 19Press RUN on the generator set controller to cycle/crank the engine (3 cycles of 15 seconds crank / 15 seconds rest) until the unit shuts down on an overcrank fault
- 20Press the OFF button on the generator set controller
- 21Pressing the OFF button during the crank cycle stops the cranking.
- 22Reconnect the green lead to the oil pressure switch
- 23Reconnect the green wire lead to the oil pressure switch terminal
- 24Reinstall the oil pressure switch and tighten to 10.7 Nm (95 in-lbs.)
- 25Reinstall the oil pressure switch using fresh pipe sealant with Teflon (Loctite PST 592 or equivalent), torquing to 10.7 N·m (95 in-lbs)
- 26Replace corroded or broken metal parts.
- 27See Section 2.6
- 28See Section 2.6 for information related to the overcrank fault.
- 29Shut off the fuel supply by closing the manual fuel valve or disconnecting lead 70A from the fuel solenoid valve
- 30System shuts down on overcrank fault.
- 31system shuts down on an overcrank fault