NEED MAN REGEN

UnclassifiedEmissions

What This Code Means

AMBER pre-alarm LED is ON or FLASHING; DPF icon is shown on the ECU display; ECU displays FILTER CLEAN REQUESTED; Basler DGC-2020HD controller displays pre-alarm NEED MAN REGEN and PRESS RUN BUTTON; Generator derating occurs; ECU displays SOOT LEVEL HIGH!; Generator shuts down; Controller displays 'FILTER CLEAN REQUESTED' message; Generator derating; Generator shutdown; Controller displays 'SOOT LEVEL HIGH!' message; Basler DGC-2020HD controller displays pre-alarm 'NEED MAN REGEN' and 'PRESS RUN BUTTON'

Possible Causes

  • DPF system soot level 3 reached
  • Manual regeneration is required
  • DPF system soot level 4 reached
  • DPF system soot level 5 reached
  • DPF Soot Level 3 accumulation
  • DPF Soot Level 4 accumulation
  • DPF Soot Level 5 accumulation
  • Manual DPF regeneration is required

Suggested Actions

  1. 1Place all circuit breakers in the OFF position.
  2. 2Press the Program/Exit button on the ECU controller and select FORCE REGEN mode.
  3. 3Press and hold the request until the REGEN ACTIVE message is displayed on the screen, then release to start forced regeneration.
  4. 4Allow the forced regeneration cycle to complete (takes 30 minutes to 1.5 hours).
  5. 5Press the RUN button for 5 seconds to initiate the Stationary Forced Regen.
  6. 6Initiate forced regeneration procedure.
  7. 7Contact your nearest authorized service center.
  8. 8Initiate a forced regeneration: Place all circuit breakers in the OFF position, press the Program/Exit button on the ECU controller, select FORCE REGEN mode, and press and hold the request until the REGEN ACTIVE message is displayed.
  9. 9Allow the engine to run for at least 30 minutes to complete the auto regeneration process.
  10. 10For Soot Level 5 shutdown, contact your nearest authorized service center.