MODULE STATUS CHANGE
UnclassifiedGeneral
What This Code Means
Controller display shows 'Module Status Change' message; Module status displays 'Status: Lost'; ATS display shows 'Module Status Change' message
Possible Causes
- •A module has been disconnected
- •A new accessory module is detected
- •A new module is detected
- •An accessory module has been disconnected
- •Cable from controller to accessory module assembly is loose or disconnected
- •Communication to an installed I/O module has been lost
- •Failure of the controller's real-time clock
- •Installing one or more accessory modules
- •Installing or reconnecting one or more accessory modules
- •Loose or disconnected cable from the controller to the accessory module assembly
- •One or more accessory modules disconnected from the controller
- •One type of module is replaced with another type of module that has the same address
- •Real-time clock failure on controller board
- •Reconnecting one or more accessory modules
Suggested Actions
- 1Attempt to reset the fault following standard reset procedures
- 2Check I/O module connections
- 3Check connections from the controller to the I/O module assembly and at the top of each I/O module
- 4Close the enclosure door and reconnect power to the ATS
- 5Connect the new module
- 6Disconnect power to the ATS
- 7Disconnect power to the transfer switch
- 8Disconnect the module
- 9Follow the procedure in the Module Status Change section to uninstall the module through the ATS controller keypad when Check Module Setup to Clear Fault is displayed
- 10If a module has been removed, go to Set Inputs/Outputs screen and uninstall the module
- 11If the procedures in the Module Status Change section fail to clear the error message, replace the controller
- 12Navigate to the Set Auxiliary I/O screen to check the status and settings for the new module
- 13Navigate to the Set Input/Outputs > Set Aux I/O screen to check that the controller has recognized the connected modules
- 14Navigate to the Set Input/Outputs > Set Aux I/O screen to verify the controller recognizes the connected modules
- 15Press Reset again
- 16Press the Reset button on the ATS display
- 17Press the Reset button on the Reset New Module screen
- 18Press the Reset button when the ATS display shows 'Module Status Change'
- 19Press the Reset button when the ATS display shows Module Status Change
- 20Press the Reset button when the screen displays 'Reset New Module'
- 21Press the button labeled Reset to display Reset New Module, then press the reset button from that screen
- 22Press the button labelled Reset when display shows Module Status Change
- 23Press the down arrow button on the Main screen to open the Reset Fault screen and press Reset
- 24Press the reset button to open Reset New Module screen
- 25Replace the controller if the fault cannot be reset
- 26See Module Status Change section to reset
- 27See the Module Status Change section to reset
- 28Verify that the cable from the controller to the accessory module assembly is not loose or disconnected
- 29Verify that the module is securely installed
- 30When 'Check Module Setup to Clear Fault' appears, press the Reset button to clear the fault