LV

UnclassifiedElectrical

What This Code Means

Battery charger fault alarm energized; Battery charger is not in constant-current mode during low battery voltage alarm condition

Possible Causes

  • •Battery voltage drops below a preset level for longer than 2 seconds
  • •One or both power SCRs open
  • •Open DC output fuse

Suggested Actions

  1. 1Contact an authorized distributor/dealer for service or service literature to make adjustments
  2. 2Raise battery voltage to the reset point (12.4–12.9 V for 12V system, 24.8–25.8 V for 24V system) to reset alarm contacts