LV
UnclassifiedElectrical
What This Code Means
Battery charger fault alarm energized; Battery charger is not in constant-current mode during low battery voltage alarm condition
Possible Causes
- •Battery voltage drops below a preset level for longer than 2 seconds
- •One or both power SCRs open
- •Open DC output fuse
Suggested Actions
- 1Contact an authorized distributor/dealer for service or service literature to make adjustments
- 2Raise battery voltage to the reset point (12.4–12.9 V for 12V system, 24.8–25.8 V for 24V system) to reset alarm contacts