GO OFFLINE FOR REGEN WARNING

UnclassifiedGeneral

What This Code Means

Hydrocarbon (HC) buildup over 50%; Hydrocarbon (HC) levels need to be reduced

Possible Causes

  • •Hydrocarbon (HC) buildup on Tier 4 generator set during operation

Suggested Actions

  1. 1Generate 'Go Offline for Regen Warning' on APM603 controller
  2. 2Shed generator set load and take offline within 90 seconds
  3. 3Activate load bank once generator set goes offline
  4. 4Activate load bank if paralleling breaker is open
  5. 5Activate load bank if generator is the only unit online and total load including load bank will not exceed 90% of generator rated power

ASK RUDY ABOUT THIS FAULT

Get a diagnosis walkthrough for GO OFFLINE FOR REGEN WARNING on your specific Rehlko unit — cited to the OEM manual, not a forum guess.

GET THE ANSWER

Free account required — we'll bring your question with you.