FAILED TO START
UnclassifiedCooling
What This Code Means
Engine fails to start during start cycle test; LCD displays 'Failed to start' after pre-set number of start attempts; Engine fails to start; Starter motor does not disengage automatically; Engine fails to run up to operating speed
Possible Causes
- •Fuel solenoid is disabled or disconnected
- •Engine is not fully operational
- •Fuel is unavailable
- •Fuel solenoid is not operating
- •Active alarm condition
- •Faulty input wiring
Suggested Actions
- 1Press the Stop/Reset Mode button to reset the unit
- 2Restore the engine to operational status by reconnecting the fuel solenoid
- 3Check that the engine is fully operational
- 4Verify fuel is available
- 5Check that the fuel solenoid is operating
- 6Check the alarm condition for validity
- 7Check input wiring