FAIL TO STOP
UnclassifiedSensors
What This Code Means
Engine does not stop when requested; FAIL TO STOP alarm is activated; Changing module modes is not possible; Remote start signals are ignored; Engine does not start; Module enters Power Save Mode; Module enters Deep Sleep Mode
Possible Causes
- •Engine fails to reach rest state (Engine speed is not zero, Generator AC Voltage and Frequency are not zero, Engine Charge Alternator Voltage is not zero, or Oil pressure sensor does not indicate low oil pressure within the Fail to Stop timer period)
- •Digital input configured to panel lock is active
- •Module is in Stop/Reset Mode
- •Module left in Stop/Reset Mode with no presses of the fascia buttons and configured for Power Save Mode
Suggested Actions
- 1Enter Auto Mode
- 2Press any fascia control buttons to wake the module
- 3Activate Digital Input A to wake the module
Related Deep Sea Electronics Fault Codes
ASK RUDY ABOUT THIS FAULT
Get a diagnosis walkthrough for FAIL TO STOP on your specific Deep Sea Electronics unit — cited to the OEM manual, not a forum guess.
TRY IT FREE