FAIL TO CLOSE DELAY HIGH

UnclassifiedTransfer Switch

What This Code Means

Contactor in the paralleling box did not close as expected; Fail to close delay high warning on controller

Possible Causes

  • •Control cable not connected correctly
  • •Fuses in the contactor close circuit not intact
  • •Pins in control harness connectors bent, damaged, or corroded
  • •Programmable digital output 1:2 or 116 in SiteTech not enabled or event not set to Contactor
  • •Wiring in generator set or paralleling box damaged or not connected correctly
  • •Control cable connected incorrectly
  • •Blown or damaged fuses in contactor close circuit
  • •Bent, damaged, or corroded pins in control harness connectors
  • •Damaged or incorrectly connected wiring in generator set or paralleling box

Suggested Actions

  1. 1Make sure control cable is connected correctly
  2. 2Verify fuses in the contactor close circuit are intact
  3. 3Inspect pins in control harness connectors for damage, bending, or corrosion
  4. 4Check programmable digital output 1:2 or 116 in SiteTech to ensure it is enabled and event is set to Contactor
  5. 5Verify wiring in generator set and paralleling box is undamaged and connected correctly
  6. 6Make sure that the control cable is connected correctly
  7. 7Inspect pins in control harness connectors to ensure they are not bent, damaged, or corroded
  8. 8Check programmable digital output 1:2 or 116 in SiteTech to ensure it is enabled and the event is set to Contactor
  9. 9Verify that wiring in the generator set and wiring in the paralleling box is undamaged and connected correctly