CHECK MODULE SETUP TO CLEAR FAULT

UnclassifiedTransfer Switch

What This Code Means

ATS display shows message 'ModuleStatusChange'; ATS display shows message 'Check Module Setup to Clear Fault'

Possible Causes

  • •One or more accessory modules are physically disconnected from the controller

Suggested Actions

  1. 1If the ATS display shows 'ModuleStatusChange', press the Reset button
  2. 2If the ATS display shows 'Check Module Setup to Clear Fault', press Main to return to the main screen
  3. 3Press Set to enter setup mode and enter the setup password
  4. 4Press the down arrow to step to the Set Inputs/Outputs screen
  5. 5Navigate to the Set Auxiliary I/O screen, press the right arrow button to see module status, and press the down arrow button until the screen shows 'Status: Lost'
  6. 6Press the right arrow button to move to the Uninstall Module screen and verify it displays 'Uninstall Module Yes'
  7. 7When 'Yes' is displayed, press Save to uninstall the module
  8. 8Repeat the uninstall procedure for additional modules if necessary