E-13766461

UnclassifiedSpeed

What This Code Means

Transient performance targets not met; Altered engine transient response; Reduced transient capability; Potential engine over-speeding

Possible Causes

  • Insufficient stabilization time between load steps (less than 180 seconds)
  • Air Fuel Ratio (AFR) control system failed to converge
  • Differences in generator inertia
  • Site-specific environmental or load conditions
  • Wear of components outside of specified tolerances
  • Local generator breaker opens during loaded condition

Suggested Actions

  1. 1Allow a minimum of 180 seconds between load steps for NOx to return to nominal setting
  2. 2Tune Engine Governor gains for site conditions
  3. 3Tune Voltage regulator settings for site conditions
  4. 4Maintain engine in accordance with guidelines specified in applicable Caterpillar Service Manuals
  5. 5Ensure engine control algorithm load sensing strategy is active to reset control inputs to rated idle condition