AUXILIARY SWITCH OPEN
UnclassifiedSensors
What This Code Means
Main shaft auxiliary switches indicate ATS is in neither position (all inputs are open)
Possible Causes
- •All inputs on main shaft auxiliary switches are open
- •Controller cannot determine the transfer switch position
- •Transfer switch in intermediate position
Suggested Actions
- 1Check the control contact operation
- 2Check the control contact operation.
- 3Check wiring and connections to position microswitches.
- 4Check wiring and connections to position microswitches. See schematic drawing for connections
- 5Inspect for signs of coil damage or overheating and replace coil if necessary
- 6Inspect for signs of coil damage or overheating and replace coil if necessary.
- 7Manually operate the transfer switch, following safety precautions and instructions for your model
- 8Manually operate the transfer switch, following safety precautions and instructions for your model.
- 9Replace microswitch if necessary.
- 10Test position microswitch operation.
- 11Test position microswitch operation. Replace microswitch if necessary
Related Rehlko Fault Codes