ANSI 40
UnclassifiedGeneral
What This Code Means
Reverse VARS; Loss of field; Loss of excitation; Under excitation relay trip; Protective relay tripping
Possible Causes
- •Voltage regulator target mismatch
- •Incorrect voltage calibration
- •Incorrect calibration of bus voltage
- •Droop settings do not match
- •Different engine types
- •Large capacitor banks used to offset motor loads on the load bus
- •Alternator damage
- •Excitation control wiring disconnected or shorted
- •Voltage sensing wiring connection problems
Suggested Actions
- 1Verify that voltage regulator target settings on the paralleled generator sets match
- 2Verify that L-L generator metering on paralleled generator sets match within 0.25% (0.5 V @ 208 VAC or 1V at 480 VAC). Use a calibrated meter to calibrate the generator set controllers, if necessary
- 3Check bus metering on the controller and use a calibrated meter to compare readings. Adjust calibration on the controller, if necessary
- 4Check the reactive droop setting on each generator set. Droop percentages should match on all paralleled generator sets
- 5Try adjusting the proportional, integral, and derivative gains for the reactive load sharing by factors of 1.5 until the protective relay does not trip or until sharing becomes unstable
- 6Disconnect capacitors when the system is powered by the generator sets or when motor load is not present
- 7Service the alternator
- 8Check and correct excitation control wiring and connections
- 9Check and correct voltage sensing wiring and connections