ANSI 40

UnclassifiedGeneral

What This Code Means

Reverse VARS; Loss of field; Loss of excitation; Under excitation relay trip; Protective relay tripping

Possible Causes

  • •Voltage regulator target mismatch
  • •Incorrect voltage calibration
  • •Incorrect calibration of bus voltage
  • •Droop settings do not match
  • •Different engine types
  • •Large capacitor banks used to offset motor loads on the load bus
  • •Alternator damage
  • •Excitation control wiring disconnected or shorted
  • •Voltage sensing wiring connection problems

Suggested Actions

  1. 1Verify that voltage regulator target settings on the paralleled generator sets match
  2. 2Verify that L-L generator metering on paralleled generator sets match within 0.25% (0.5 V @ 208 VAC or 1V at 480 VAC). Use a calibrated meter to calibrate the generator set controllers, if necessary
  3. 3Check bus metering on the controller and use a calibrated meter to compare readings. Adjust calibration on the controller, if necessary
  4. 4Check the reactive droop setting on each generator set. Droop percentages should match on all paralleled generator sets
  5. 5Try adjusting the proportional, integral, and derivative gains for the reactive load sharing by factors of 1.5 until the protective relay does not trip or until sharing becomes unstable
  6. 6Disconnect capacitors when the system is powered by the generator sets or when motor load is not present
  7. 7Service the alternator
  8. 8Check and correct excitation control wiring and connections
  9. 9Check and correct voltage sensing wiring and connections