ALARM #38

UnclassifiedCooling

What This Code Means

Equipment has been turned off; Immediate shutdown occurs; System issues an alarm; Operating mode shuts down; Alarm runs continuously; High inverter temperature warning occurs; Output overload warning occurs; System shuts the operating mode down; Error LEDs are on (red); Error persists after restart; Excessive discharge of the battery; Excessive charge of the battery; Equipment shutdown

Possible Causes

  • One of the phases has been turned off
  • One of the inverters turned off during its operation
  • Erroneous synchronization between the inverters
  • Failure of real-time communications
  • High inverter temperature
  • Output overload
  • BMS of the batteries detects that a battery cell has a voltage lower than acceptable
  • BMS of the batteries is defective
  • Incorrect communication between battery BMS and Cerbo GX
  • Loose or damaged RJ45 connectors
  • Battery is defective
  • One or more cells of the batteries are defective
  • One of the phases has been disabled

Suggested Actions

  1. 1Refer to the on-screen help
  2. 2See 7.Warning and Alarms
  3. 3Perform a complete restart of the EHR equipment
  4. 4Refer to the steps indicated in the on-screen help
  5. 5See 5. Starting up the EHR plant
  6. 6Deal with the warning by referring to the on-screen help
  7. 7Refer to 7.Warning and Alarms
  8. 8Check to see if the error LEDs are on (red) and identify the defective elements
  9. 9Check that the communication between the BMS of the batteries and the Cerbo GX is correct
  10. 10Check that the RJ45 connectors connected between the battery modules are in good condition and tight
  11. 11Check the voltage between the DC bus from the EHR
  12. 12Turn the batteries off and restart the equipment
  13. 13Replace defective modules
  14. 14Refer to the manual to perform a system shutdown (do not turn the batteries off)
  15. 15Check that the batteries are working properly and see if the error LEDs are on (red) to identify defective elements
  16. 16Check that the RJ45 connectors connected between the battery modules are in good condition and tightly tightened
  17. 17Charge the batteries by applying an operating mode or by performing a maintenance charge