ALARM #38
UnclassifiedCooling
What This Code Means
Equipment has been turned off; Immediate shutdown occurs; System issues an alarm; Operating mode shuts down; Alarm runs continuously; High inverter temperature warning occurs; Output overload warning occurs; System shuts the operating mode down; Error LEDs are on (red); Error persists after restart; Excessive discharge of the battery; Excessive charge of the battery; Equipment shutdown
Possible Causes
- •One of the phases has been turned off
- •One of the inverters turned off during its operation
- •Erroneous synchronization between the inverters
- •Failure of real-time communications
- •High inverter temperature
- •Output overload
- •BMS of the batteries detects that a battery cell has a voltage lower than acceptable
- •BMS of the batteries is defective
- •Incorrect communication between battery BMS and Cerbo GX
- •Loose or damaged RJ45 connectors
- •Battery is defective
- •One or more cells of the batteries are defective
- •One of the phases has been disabled
Suggested Actions
- 1Refer to the on-screen help
- 2See 7.Warning and Alarms
- 3Perform a complete restart of the EHR equipment
- 4Refer to the steps indicated in the on-screen help
- 5See 5. Starting up the EHR plant
- 6Deal with the warning by referring to the on-screen help
- 7Refer to 7.Warning and Alarms
- 8Check to see if the error LEDs are on (red) and identify the defective elements
- 9Check that the communication between the BMS of the batteries and the Cerbo GX is correct
- 10Check that the RJ45 connectors connected between the battery modules are in good condition and tight
- 11Check the voltage between the DC bus from the EHR
- 12Turn the batteries off and restart the equipment
- 13Replace defective modules
- 14Refer to the manual to perform a system shutdown (do not turn the batteries off)
- 15Check that the batteries are working properly and see if the error LEDs are on (red) to identify defective elements
- 16Check that the RJ45 connectors connected between the battery modules are in good condition and tightly tightened
- 17Charge the batteries by applying an operating mode or by performing a maintenance charge