2801

UnclassifiedElectrical

What This Code Means

Battery voltage is above 16.1Vdc; Battery voltage is less than 12.5 VDC after completing 26 hour charge cycle; AC input to battery charger missing for greater than 5 minutes during charging; Controller wrote to the EEPROM more than 500 times in less than 4 minutes; Config computed CRC unequal to stored EEPROM CRC; Generator Emergency Shutdown Switch button was pressed; AUX shutdown; Auxiliary shutdown or onboard rocker switch on Power Zone 410 front panel button was pressed and prompted a shutdown; Shutdown detected when pressed for greater than 300 ms; Common shutdown alarm indicator true for 1 second from one of the configured I/O Extender modules; Alarm detected on any digital input of connected IO Extender configured as General Alarm; NFPA20 Shutdown Inhibit is enabled and active; Shutdown alarms will be inhibited per NFPA20 requirement; Active Fault

Possible Causes

  • Charging system issue
  • AC power loss to charger
  • EEPROM abuse
  • EEPROM CRC mismatch
  • Emergency Stop button activation
  • AUX shutdown activation
  • Auxiliary shutdown switch activation
  • Power Zone 410 front panel button press
  • External I/O Extender alarm
  • General Alarm on Digital Input of IO Extender
  • NFPA20 Shutdown Inhibit enabled
  • ECODE

Suggested Actions

  1. 1Address charging system
  2. 2Test 120 Volt Input (T1) page 169
  3. 3Power cycle controller.
  4. 4If problem persists, replace controller
  5. 5Test 29 – Emergency Stop Relay (ESR) Test page 75
  6. 6Reset Aux shutdown switch
  7. 7Review alarm log and address active alarms.
  8. 8View Fault Codes