2680
What This Code Means
O2 sensor stuck open/closed; Low fuel level; Low fuel pressure; Fuel in the outer basin tank; Battery voltage below 12.1V for greater than 60 seconds; Completed 26 hour charge cycle, battery voltage below 12.52V, or current draw from charger still greater than 600 mA; Battery voltage above 16.1V; AC input to battery charger missing for greater than five minutes during charging; Controller wrote to the EEPROM more than 500 times in less than four minutes; Air/fuel mix is too rich for more than 10s; Air/fuel mix is too lean for more than 60s; Low Fuel Level; Low Fuel Pressure; Governor in open position for greater than one second; Command and position feedback not matching or taking too much time to achieve; Governor in closed position (commanded otherwise) for greater than one second; No message received for 1 second on CAN bus during startup; 12/24V Battery Type system mismatch; No response from I/O Extender 1 for 3 seconds; No response from I/O Extender 2 for 3 seconds; No response fr
Possible Causes
- •DTC logged in eeprom
- •Fuel level above 10% but lower than 20% for greater than 60 seconds
- •Low fuel pressure detected for greater than 60 seconds
- •Ruptured tank
- •Low battery
- •Battery Problem
- •Charger Warning
- •Charger Missing AC
- •EEPROM Abuse
- •Gaseous Emissions
- •Ruptured Tank
- •Governor wire loose
- •Governor module
- •Problem with CAN bus interface
- •Dealer Config and the Digital Input for confirming a 12/24 V Battery Type system mismatch
- •Loss of communication with I/O Extender 1
- •Loss of communication with I/O Extender 2
- •Loss of communication with I/O Extender 3
- •Loss of communication with I/O Extender 4
- •External Charger Failure
Suggested Actions
- 1Warning will clear after engine runs with no DTC codes three times
- 2System detected fuel in the outer basin tank and has triggered the warning
- 3The system detected fuel in the outer basin tank and has triggered the warning.
- 4Test 68 – Check Actuator and Mixer Function page 163
- 5Test 106 – Test CAN bus Communication page 174
- 6Confirm battery type settings
- 7Inspect RS-485 wiring/terminating jumper on I/O
- 8Confirm external charger settings on controller menu
- 9Check external battery charger
- 10Check Fuel Level
ASK RUDY ABOUT THIS FAULT
Get a diagnosis walkthrough for 2680 on your specific Generac unit — cited to the OEM manual, not a forum guess.
TRY IT FREE