What This Code Means
O2 sensor stuck open/closed; Low fuel level; Low fuel pressure; Fuel in the outer basin tank; Battery voltage below 12.1V for greater than 60 seconds; Completed 26 hour charge cycle, battery voltage below 12.52V, or current draw from charger still greater than 600 mA; Battery voltage above 16.1V; AC input to battery charger missing for greater than five minutes during charging; Controller wrote to the EEPROM more than 500 times in less than four minutes; Air/fuel mix is too rich for more than 10s; Air/fuel mix is too lean for more than 60s; Low Fuel Level; Low Fuel Pressure; Battery voltage is above 16.1Vdc; Battery voltage is less than 12.5 VDC after completing 26 hour charge cycle; AC input to battery charger missing for greater than 5 minutes during charging; Controller wrote to the EEPROM more than 500 times in less than 4 minutes; Config computed CRC unequal to stored EEPROM CRC; Generator Emergency Shutdown Switch button was pressed; AUX shutdown; Auxiliary shutdown or onboard ro
Possible Causes
- •DTC logged in eeprom
- •Fuel level above 10% but lower than 20% for greater than 60 seconds
- •Low fuel pressure detected for greater than 60 seconds
- •Ruptured tank
- •Low battery
- •Battery Problem
- •Charger Warning
- •Charger Missing AC
- •EEPROM Abuse
- •Gaseous Emissions
- •Ruptured Tank
- •Charging system issue
- •AC power loss to charger
- •EEPROM abuse
- •EEPROM CRC mismatch
- •Emergency Stop button activation
- •AUX shutdown activation
- •Auxiliary shutdown switch activation
- •Power Zone 410 front panel button press
- •External I/O Extender alarm
Suggested Actions
- 1Warning will clear after engine runs with no DTC codes three times
- 2System detected fuel in the outer basin tank and has triggered the warning
- 3The system detected fuel in the outer basin tank and has triggered the warning.
- 4Address charging system
- 5Test 120 Volt Input (T1) page 169
- 6Power cycle controller.
- 7If problem persists, replace controller
- 8Test 29 – Emergency Stop Relay (ESR) Test page 75
- 9Reset Aux shutdown switch
- 10Review alarm log and address active alarms.