2399
UnclassifiedCooling
What This Code Means
Unit is overloaded; Unit was overloaded and attempted to start with a large load connected; Unit can not ramp up the generator voltage to its normal target voltage value if it starts with a large load connected
Possible Causes
- •Current flow in stepper coil(s) above specification
- •One of the two CTs is detecting an overload condition
- •Starting with a large load connected
- •Stepper overcurrent
Suggested Actions
- 1Change load dynamics
- 2Check transfer switch loadshed functionality
- 3Perform Test 12
- 4Remove Load
- 5Utilize loadshed