214
UnclassifiedGeneral
What This Code Means
HIGH BATTERY warning displayed; Control battery voltage supply approaching high level; Risk of damage to control
Possible Causes
- •Battery voltage is above the high voltage threshold (out of preset operating range) during normal operation
- •Battery voltage supply to the control approaching a high level
- •Fault condition
Suggested Actions
- 1Correct the fault condition prior to acknowledging the fault
- 2If equipped with an operator panel, press the button on the panel to acknowledge/clear the fault
- 3If in Auto mode, use an external customer-supplied remote fault reset switch (requires setting 'Remote Fault Reset Enabled' trim to 'Enabled' using InPower, mapping a configurable input to 'Fault Reset', and removing the remote start command prior to activating the reset switch)
- 4If not equipped with an operator panel, place the Auto/Off/Manual Run switch in the Off position